Table 310.16 · screening
Read the Table 310.16 ampere column.
Pick the temperature column. Most breakers and lugs are 60°C or 75°C, so the circuit is usually limited to those. 90°C is the insulation rating.
Calculated results
| Size | Amperes at 75°C |
|---|---|
| 14 | 20 A |
| 12 | 25 A |
| 10 | 35 A |
| 8 | 50 A |
| 6 | 65 A |
| 4 | 85 A |
| 3 | 100 A |
| 2 | 115 A |
| 1 | 130 A |
| 1/0 | 150 A |
| 2/0 | 175 A |
| 3/0 | 200 A |
| 4/0 | 230 A |
| 250 | 255 A |
| 300 | 285 A |
| 350 | 310 A |
| 400 | 335 A |
| 500 | 380 A |
| 600 | 420 A |
| 750 | 475 A |
| 1000 | 545 A |
What this sheet does
- This page does not size a job. It shows how many amperes each wire can carry.
- Pick copper or aluminum, then 60°C, 75°C, or 90°C.
- Each row is a wire size and the amperes for the temperature you picked.
- On a normal circuit, 14 AWG copper stops at 15 A, 12 AWG at 20 A, and 10 AWG at 30 A. A motor circuit is one case where the breaker can be higher than that.